- Protocol & Hierarchy: DP-V0 Slave
- Supports PROFIBUS Transmission Rate (kbps):6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, 12000
- Transmission Rate Setting: detected automatically
- Max Input Data Length: 240 Bytes
- Max Output Data Length: 240 Bytes
- Address Setting: 0~126 set by DIP switch or EEPROM
- Supports HART Mode: point-to-point / multi-drop
- Support HART Master: Allow two HART Masters
- Support HART Channel: 4 channels
- Support HART Frame: Short/Long frame
- Support HART modules: Connecting up to 15 HART modules
- Support HART Burst mode: YES
- Indicators: PWR, ERR, and RUN LEDs
- Network Isolation Protection: 2500 Vrms High Speed iCoupler
- DC Isolation Protection: 3000 VDC on PROFIBUS side
GW-7557
The GW-7557 Gateway is specially designed for the slave device of PROFIBUS DP protocol. It allows the PROFIBUS master to access the HART slave devices. These HART slave devices may be a transmitter, an actuator, a current output device and so forth. In addition, we also provide the utility software for users to configure the GW-7557. By using this module, users can put their HART slave devices into PROFIBUS network very easily.
See the Product PDF Datasheet for Full Specifications.
GW-7557-B CR: PROFIBUS/HART Gateway (RoHS)
GW-7557-M CR: PROFIBUS/HART Gateway (RoHS) (Metal casing)
- ICP DAS