- Protocol & Hierarchy: DP-V0 Slave
- Supports PROFIBUS Transmission Rate (Kbps):6, 19.2, 45.45, 93.75, 187.5, 500, 1500, 3000, 6000, 12000
- Transmission Rate Setting: detected automatically
- Max Input Data Length: 132 Bytes
- Max Output Data Length: 131 Bytes
- Address Setting: 0~126 set by DIP switch
- Supports Modbus Mode: Master/Slave
- Supports Modbus Format: RTU/ASCII
- Hybrid COM 1: RS-232/422/485 with “Self Tuner” inside
- Supports COM 1 Baudrate (Kbps):4, 4.8, 9.6, 19.2, 38.4, 57.6, 115.2
- Supports COM 1 Data Format: 7/8 data bits, No/Odd/Even parity, 1/2 stop bit
- Indicators: PWR, ERR, and RUN LEDs
- Network Isolation Protection: High Speed iCoupler
- DC Isolation Protection: 3000VDC on PROFIBUS side
GW-7552
The GW-7552 Gateway is specially designed for the slave device of PROFIBUS DP protocol. It allows the PROFIBUS master to access the Modbus devices. These Modbus devices may be a PLC, a sensor, ICPDAS M-7000 series modules and so forth. In addition, we also provide the utility software for users to configure the GW-7552. By using this module, users can put their Modbus devices into PROFIBUS network very easily.
See the Product PDF Datasheet for Full Specifications.
GW-7552-B CR: PROFIBUS/Modbus Gateway (RoHS)
GW-7552-M CR: PROFIBUS/Modbus Gateway (RoHS) (Metal casing)
- ICP DAS